Generator engines give off deadly carbon monoxide gas through
their exhaust systems.
Carbon monoxide gas, if breathed in sufficient concentrations,
can cause unconsciousness or death. Exhaust gases must be piped
safely away from any room or enclosure that houses a generator and
to a well ventilated area where people will not be endangered.
Besides the possibility of carbon monoxide poisoning, exhaust
piping becomes extremely hot during operation and remains hot for
a long time after shutdown. For that reason, the following
precautions are necessary:
7-2. General Rules for Exhaust Systems
When installing an exhaust system for a generator, the following
rules should be considered:
7-3. Routing Exhaust Piping Through Combustible Walls
Figure 10. Wall Thimble
7-4. Routing Exhaust Piping Through Combustible
Roofs
Exhaust piping that passes through any combustible roof must be
separated from the roof by a ventilated metal thimble that is at
least 6 inches in diameter larger than the piping. The thimble
must extend at least 9 inches (229mm)(10 inches (250mm)
recommended) above and below roof construction.
Figure 11. Roof Thimble

7-5. Rain Cap
A rain cap is recommended on the end of the exhaust pipe. The
rain cap is attached to the end of the pipe and opens due to the
pressure from the exhaust discharge force. The rain cap protects
the exhaust system from the environment when the system is not
running.
7-6. Spark Arrestor
Use of a spark arrestor is required by the U.S. Department of
Forestry if located on lands under their jurisdiction. The spark
arrestor is recommended in areas where combustible materials may
ignite such as dry grass, leaves, or other combustible materials.
The exhaust back pressure of the generator when measured at full
load must not exceed the manufacturer's recommendations. The size
of exhaust pipe, number and type of ends and fittings together
with the selection and location of muffler determine exhaust back
pressure.
A typical 90 degree bend in an exhaust system is equal to adding
8 feet (2.67 meters) of pipe.
SECTION 8 - Gaseous Fuel Systems
8-1. General (Gaseous
Fuel Systems)
Some generators are equipped with fuel systems that utilize
Liquefied Petroleum (LP) or Natural Gas as a fuel.
Local fuel gas codes may vary widely. For that reason, it is
recommended that a local gas distributor or installer be consulted
when installing a gaseous fuel supply system. In the absence of
local fuel gas codes and regulation, booklets published by the
National Fire Protection Association (NFPA) may be used as sources
of information.
The installer must ensure that the correct fuel delivery system
is installed, and that applicable standards and codes are strictly
complied with.
8-2. Advantages of
Gaseous Fuels
Use of Natural and LP gas as a fuel may result in a slight power
loss. However, that disadvantage is usually compensated for by the
many advantages of gaseous fuels. Some of the advantages of
gaseous fuels are:
Low residue content, resulting in minimum carbon formation.
8-3. Gaseous Fuel System Variations
Any one of four different types of gaseous fuel systems may
typically be installed by the factory on your generator system,
dependent upon the model. These are:
8-4. Properties of
Gaseous Fuels
Natural Gas: Is lighter than air and tends to settle in
high places. Natural gas is found in the gaseous state only at
normal ambient conditions. Natural gas is highly explosive and
accumulations of the gas can be ignited at the slightest spark.
For that reason, adequate ventilation is absolutely essential and
fuel lines must be free of leaks. Local fuel/gas codes usually
dictate the maximum pressure at which natural gas can enter a
structure. A primary regulator is required, to reduce the pressure
of the delivered gas to the reduced pressure required by code.
LP Gas: Is heavier than air, tends to settle in low
places. The gas is highly explosive and the slightest spark can
cause an explosion. LP gas is usually supplied in pressure tanks
as a liquid, but is found in gaseous form at normal atmospheric
temperature and pressure. It may consist of (1) butane, or (2)
propane, or (3) a mixture of these two gases. Fuel suppliers may
fill the supply tank with a mixture made up primarily of butane in
warm weather. Butane may not provide sufficient vapor pressure in
colder weather and more propane may have to be added to the
mixture. The ratio of butane to propane is especially important
when a large outdoor supply tank is used. LP gas must be converted
to its vapor state before it enters the engine carburetor.
The maximum pressure at which natural gas can enter the building
is established by code and may vary from area to area. The gas
distribution company will usually provide piping from the main
distribution line to the standby generator site. A primary
regulator is needed to reduce gas supply pressures to the required
safe level before the gas enters a building. Such a regulator may
or may not be provided by the gas supplier. It is the
responsibility of the gas supplier to ensure that sufficient gas
pressure is available to operate the primary regulator.
Gas outlet pressure from the primary regulator to the standby
generator's shutoff valve should typically not exceed
approximately 0.50 pounds per square inch (psi), or 14 inches of
water column. Optimum supply pressure to most small generator's
shutoff valve is 11 inches of water column. Depending on the
characteristics of the specific shutoff valve in use, the valve
may or may not open at supply pressures greater than 0.50 psi (14
inches water column).
Install a flexible length of fuel line between rigid piping
and the Generator engine's natural gas connection point.
Natural gas is delivered to the primary regulator. From the
primary regulator, in most installations, the gas flows through a
solenoid operated fuel shutoff valve, a pressure reducing valve
and the engine's natural gas carburetor. The shutoff valve is
electrically energized open during startup and running, is
de-energized closed on shutdown. The carburetor measures engine
air flow and meters gas to the engine based on throttle setting
and load. The carburetor also provides a positive gas shutoff.
8-6. LP Gas Vapor
Withdrawal System
This type of system utilizes the vapors formed above the liquid
fuel in the supply tank. Approximately 10-20 percent of the tank
capacity is needed for fuel expansion from the liquid to the vapor
state.
Ambient temperatures around the supply tank must be high enough
to sustain adequate vaporization or the system will not function
properly. In addition to the cooling effects of ambient air, the
vaporization process itself provides an additional cooling effect.
Vapor withdrawal systems are generally more suited for smaller
engines that need less fuel.
When ambient temperatures are low and fuel consumption is high,
the vapor withdrawal system may not function efficiently. This is
particularly true with larger engine machines.
Many LP gas and Natural Gas vaporous fuel systems are identical
as a demand regulator is used to provide fuel to the engine.
8-7. LP Liquid Withdrawal
System
This type of system delivers gas in liquid form to a generator.
The liquid fuel must then be vaporized before it is delivered to
the engine carburetor.
Liquid withdrawal (LP) gas systems usually employ a
"vaporizer-regulator" to convert the liquid to its vapor state. A
"vaporizer-regulator" is mounted in the air flow of the engine to
provide heat to the regulator for fuel vaporization.
LP liquid withdrawal is typically used for equipment used in
remote locations where size and availability of refilling the tank
is limited. Liquid withdrawal is also used for trailered and
construction site equipment.
8-8. Dual Natural/LP
Gas Fuel System
In some areas, the cost of Natural gas may be reduced
considerably by procuring the gas on "interrupted service" rates.
Such "interrupted service" can be obtained by using LP gas as an
emergency fuel whenever Natural gas is not available.. Automatic
changeover is accomplished by using two regulators - a line
pressure regulator for natural gas and a vacuum operated regulator
for LP gas. The differences in pressures compensates for the
greater BTU value of LP gas.
During operation on Natural gas, a 5 inch (water column)
(typical) pressure exists in the common line to the carburetor.
This pressure closes the LP gas regulator. Loss of Natural gas
pressure causes loss of pressure in the line; the LP gas regulator
then opens to admit LP gas into the system. A separate power
mixture adjustment in the LP gas line provides precise setting of
air/fuel ratios for each of the two fuels. Changeover is automatic
with the engine operating.
8-9. Gaseous Fuel System
Piping
The following general rules apply to piping used in gaseous fuel
systems:
NOTE: In the absence of local purging and leak test
standards, NFPA No. 54 may be used as a guide.
8-10. Gaseous Fuel Pipe Sizes
A "Gas Flow Pipe Sizing Chart" (Table 8-1)
is provided below. Use the chart to determine the correct piping
diameter in gaseous fuel systems (such as Natural gas and LP gas
vapor withdrawal type).
To find the proper pipe diameter, the installer must know (a)
the length of the gas piping run, and (b) the cubic feet of gas
needed by the generator when under full load.
First, find the length of the piping run on the chart.
From the pipe length figure on the chart, move horizontally
across the chart until you reach a number that is just higher than
the cubic feet of gas needed under full load. From the cubic feet
of gas figure, move straight up vertically in the chart to the
pipe diameter given in that vertical column. This is the pipe size
required.
LP Gaseous Fuel Example: A small 16 horse power
generator when operating at full load requires a supply of 51
cubic feet per hour of LP gas. Length of the piping run from the
supply tank is 60 feet. Propane gas having a specific gravity of
1.5 and with a multiplier of 0.633 is used (Table
8-2). From the pipe length in the chart, trace horizontally
across to "86" (the first number larger than 51 cubic feet).
Moving vertically upward in the chart, a 3/4 inch pipe is needed.
Applying the chart conversion factor (86 x 0.633=54.44) and the
3/4 inch pipe is still adequate.
Natural Gas Example: A small 16 horse power generator operating at full load requires 115 cubic feet per hour of Natural gas. Length of the piping run from the supply tank is 75 feet. Natural gas having a specific gravity of 0.65 and with a multiplier of 0.962 (Table 8-2) is to be used. From the pipe length in the chart, trace horizontally across to "155" (the first number larger than 115 cubic feet). Moving vertically upward in the chart, a 1 inch pipe is required. Apply the conversion factor (155 x 0.962=149.1) and the 1 inch pipe is still adequate.
|
Table 8-1. Gas Flow Pipe Sizing Chart |
|||||||||||
|
Length of |
1/2 In. |
3/4 In. |
1 In. |
1-1/4 In. |
1-1/2 In. |
2 In. |
2-1/2 In. |
3 In. |
4 In. |
6 In. |
8 In. |
|
15/4.57 |
76 |
172 |
345 |
750 |
1220 |
2480 |
3850 |
6500 |
13880 |
28700 |
79000 |
|
30/9.14 |
52 |
120 |
241 |
535 |
850 |
1780 |
2750 |
4700 |
9700 |
27370 |
55850 |
|
45/13.72 |
43 |
99 |
199 |
435 |
700 |
1475 |
2300 |
3900 |
7900 |
23350 |
45600 |
|
60/18.29 |
38 |
86 |
173 |
380 |
610 |
1290 |
2000 |
3450 |
6800 |
19330 |
39500 |
|
75/22.86 |
|
70 |
155 |
345 |
545 |
1120 |
1750 |
3000 |
6000 |
17310 |
35300 |
|
90/27.43 |
|
77 |
141 |
310 |
490 |
1000 |
1560 |
2700 |
5500 |
15800 |
32250 |
|
105/32.00 |
|
65 |
131 |
280 |
450 |
920 |
1430 |
2450 |
5100 |
14620 |
29850 |
|
120/36.58 |
|
|
120 |
270 |
420 |
860 |
1340 |
2300 |
4800 |
13680 |
27980 |
|
150/45.72 |
|
|
109 |
242 |
380 |
780 |
1220 |
2090 |
4350 |
12240 |
25000 |
|
180/54.86 |
|
|
100 |
225 |
350 |
720 |
1120 |
1950 |
4000 |
11160 |
22800 |
|
210/64.01 |
|
|
92 |
205 |
320 |
660 |
1030 |
1780 |
3700 |
10330 |
21100 |
|
240/73.15 |
|
|
|
190 |
300 |
620 |
970 |
1680 |
3490 |
9600 |
19740 |
|
270/82.30 |
|
|
|
178 |
285 |
580 |
910 |
1580 |
3250 |
9000 |
18610 |
|
300/91.44 |
|
|
|
170 |
270 |
545 |
860 |
1490 |
3000 |
8500 |
17660 |
|
450/137.16 |
|
|
|
140 |
226 |
450 |
710 |
1230 |
2500 |
7000 |
14420 |
|
600/182.88 |
|
|
|
119 |
192 |
390 |
900 |
1030 |
2130 |
6000 |
12480 |
|
Table 8-2. Chart Conversion Factors |
|||||
|
Specific |
Multiplier |
Specific |
Multiplier |
Specific |
Multiplier |
|
0.50 |
1.100 |
0.700 |
0.926 |
1.200 |
0.707 |
|
0.55 |
1.040 |
0.800 |
0.867 |
1.400 |
0.655 |
|
0.60 |
1.000 |
0.900 |
0.817 |
1.500 |
0.633 |
|
0.65 |
0.962 |
1.000 |
0.775 |
1.700 |
0.594 |
|
Note 1: Use of elbows
increases pressure drop on fuel lines. A 90 degree
elbow adds 3 to 8 feet of equivalent length to your
pipe estimate. |
|||||
Go to APPENDIX A - Applicable Codes
Tips on Hooking up a Generator (genset) to a Uninterruptible Power System (UPS)
Amazon.com now has tools, tooling and power generators in their Amazon.com's Tool & Home Improvement Store. Click on Amazon's Tool & Home Improvement Store or the logo above to go there or use the Search feature.
If you have questions or comments relating to this flowcharting information, please click here to email the author.