SECTION 5 - Fuel
5-1. Gasoline
For gasoline egine generators, Unleaded or Regular gasoline with
a lower octane rating than 85((RON/MON)/2) may cause
pre-detonation (knocking) which can damage the engine. Regular
gasoline can be used, however, unleaded gasoline is preferred
because it reduces pollution and combustion chamber deposits. See
the generator's engine owner's manual for fuel information or
contact the generator set's manufacturer.
|
|
ENGINE FUEL can cause fire or explosion. |
|
|
POOR QUALITY, LOW OCTANE FUEL can damage the engine. |
IMPORTANT:
5-2. Gaseous Fuels
Typically on LP Gaseous or Natural Gas powered unit the unit
will run on either vaporous fuel source. Most gaseous fuel units
are set up for a specific number of ounces of line pressure
(a.k.a. as a corresponding number Inch Water Column) with some
type of threaded pipe hook up. Note: Use of gaseous fuels decrease
the amount of total power the generator is capable of producing by
as much as 20 percent, dependent upon thermal content of fuel in
your specific area. Refer to Section 8 for Gaseous Fuel Systems.
5-3. Diesel Fuel Piping and Filtration
The basic requirements of a diesel engine fuel system are
adequate piping, proper selection of filters for the application
and completely air-tight joints, with a minimum number of fittings
to prevent air from entering the fuel lines, especially in
installations where the fuel tank is lower than the pump.
5-3. A. Piping to the Tank
Vacuum at the transfer pump inlet must be avoided. If an
auxiliary pump is used, pressure at the transfer pump must not be
less than 0 p.s.i. nor greater than 5 p.s.i.(typical). Pressure
after the return line connector assembly must not exceed 5 p.s.i.
unless called for in the pump or system specification.
NOTE: The return line must never be piped back to the transfer
pump inlet side. Both supply and return line should be connected
to standpipes in the tank with the opening for each 2 inches
minimum from the bottom of the tank to allow space for water and
sediments to settle and to eliminate siphoning problems.
Pressure drop across clean filters should not be more than 2.5
inches of mercury (1.2 p.s.i.) at full load. Pressure drop in the
supply system exceeding 10 inches of mercury (4.9 p.s.i.) because
of dirty filters or other restriction usually will affect pump and
engine performance, (erratic operation, low power, engine stall).
5-4. Fuel
Consumption
Fuel consumption is typically specified in the generator's user
manual and is specified in a quantity of fuel consumed per hour
based on a specified load. Refer to the generator's user manual
for expected fuel consumption, which is based upon a specific
load. While the generator's manufacturer may not be able to
predict the consumption for your site because of the differences
in the typical load, by site, an estimate a full load is typically
given.
A simple fuel consumption model that is a "ball park" predictor
of fuel consumption is as follows:
Based on experience, a generator at no load typically uses about
half of the fuel of a generator at full load. The ratio of output
power from a generator to the amount of fuel consumed is almost
linear. Consumption on diesel fueled generators is somewhat less
than gasoline.
Fuel Consumption = (Estimated Load/Maximum Generator Power
Output) X .5 X Maximum Fuel Consumption + 50% of Maximum Fuel
Consumption
Assuming Maximum fuel consumption = 1 Gallon/Hour
Minimum fuel consumption = .5 Gallon/Hour
At a 50% load, Fuel Consumption = (((50 Amps/100 Amps) X .5
Gallon) + .5 Gallon) = (((.5) X .5) + .5) = .75 Gal./Hr.
Other factors that need to be taken into account are the
temperatures of the areas where the fuels are stored are as
follows:
SECTION 6 - Electrical
System
There are a number of different generator systems and typical loads in the context of electrical systems. Most systems, unless they contain automated swtich gear, have a means of disconnect between the generator and the load. This is typically a transfer switch or disconnect. Ensure the contacts on the switch are rated for the size of your system. System schematics are beyond the context of this tutorial at this time.
6-1. General
(Electrical System)
Generators are rated for a maximum current in Amps and power
output in Kilowatts. Typically power outputs can vary between
different models. The output is dependent upon fuel type, ambient
temperature and altitude of the installation.
Of same model types using different fuels, Gasoline units will
have the highest output followed by gaseous fuels (Natural Gas and
Liquid Petroleum(Vapor withdrawal). LP is about 95% of that of
gasoline and natural gas at about 85% of gasoline. These units
typically derate at about 3% per 1,000 ft (334 meters) starting at
about 3,000 feet (1,000 meters) and an additional 1% for every 10
degrees over 78 degrees F. This is fairly common for all
asperating engines.
Diesel units derate more for temperature and altitude. Diesels
typically derate at about 4% per 1,000 ft (334 meters) starting at
sea level and an additional 1% for every 10 degrees over 78
degrees F. At higher elevations, this power loss can be
significant.
Circuits to carry power from the generator needs to be sized accordingly. Distance of the generator to the load (Typically a UPS) will also effect wire size. The conduit entryway for the generator is typically specified for a nominal size and may need to be increased in size if you are required to go to the maximum wire size. Flexible liquid tight metallic conduit should be used.
Direct Current (D.C.) Generators typically require a
significantly larger cable size from the generator to the load
(typically UPS batteries) in order to compensate for voltage drop.
Voltage drop is a function of the resistance of the wire
over the distance from the source to the load. The typical
recommedation for D.C. generators is to keep the generator as
close to the load as possible. Refer to the generators
manufacturer's recommendations. Refer to N.F.P.A. 70, also
known as the National Electric Code (NEC) for cable sizing tables.
When mounting electrical panels, a 3 foot clearance is required
and the use of an emergency light to illuminate the unit during
operation is typically required. Power for the emergency
light should be from both the primary utility and the generator.
This is highly recommend so that in the event of a malfunction
there is a light source to see to work on the unit. Refer to
your local building and electrical codes to ensure compliance.
Use of powered exhaust fans and powered louvers for ventilation
is typical for indoor installations. Emergency power will be
needed operate the auxillary devices. Make sure the
generator is sized large enough to cover the load and the
auxillary equipment.
6-2. Conductor
Sizing Connection
This information is dependent upon your generator output and
intended load. When connecting cables to the generator, unless
instructed differently by the equipment manufacture, make
connections at the generator first. Make the connections at the
load last. Failure to do so may constitute a fire or safety
hazard.
All ampacities are typically calculated at 75 o C
(Celsius)(167 o F(Fahrenheit) in the conductor size
charts. Building wire conductors should be rated at 90oC(194oF)
to allow for different ambient temperatures that these conductors
may pass through.
All conductors are typically required by electrical code to be
copper. The recommended conductor sizes are based on maximum
current. Ampacities are found in NEC Article 310, Table 310-16.
Conductor resistances are found in NEC Table 8 "Conductor
Properties".
Direct Current (D.C.) generators require larger output power
cables than comparable A.C. generators due to voltage drops in the
cable caused by increased resistance.
Most A.C. Generators require the use of transfer switches. Refer
to manufacturer's installation instructions and recommendations.
Tips on Hooking up a Generator (genset) to a Uninterruptible Power System (UPS)
Amazon.com now has tools, tooling and power generators in their Amazon.com's Tool & Home Improvement Store. Click on Amazon's Tool & Home Improvement Store or the logo above to go there or use the Search feature.
If you have questions or comments relating to this flowcharting information, please click here to email the author.