SECTION 4 - Ventilation
4-1. Outdoor Installations - Air Cooled Units
The following general rules apply:
Figure 4 . Typical Outside Small Generator Installation

4.2 Indoor
Installations - Air Cooled Units
When a generator is installed and operated in an indoor
environment, adequate ventilation for heat dissipation and
combustion is required. Ventilation is typically done through the
use of an air inlet, air outlet/exhaust fan, and/or other
ventilation openings.
The following rules apply:
4-3. Ventilation Exhaust Fans and Air Inlet Louvers
Some indoor installations may require the use of one or more
exhaust fans, to provide adequate ventilation during generator
operation.
The following rules apply:
4-4. Ducting of Air
The engine cooling fan moves a large volume of air during
operation. This heated air must be expelled to the outside of any
structure housing a generator.
The following rules apply to the ducting of heated engine air
out of a building:
Figure 5. Typical Indoor Ventilation Duct

Figure
7. Typical Indoor Larger Generator Installation
Roof mount radiators on liquid cooled units is sometimes done where the installation location of the unit can not dissipate the heat generated by the unit during operation. Roof mount radiators is beyond the scope of this publication.
4-5. Louvers, Screening And Expanded Metal
When louvers, screening or expanded metal are used to cover air
openings in buildings housing generators, consideration must be
given that these materials do not restrict the free flow of
cooling air. Any restriction must be compensated for by making the
actual opening size proportionately larger.
Louvers: Either fixed or movable louvers may be installed on the
air openings in a structure that houses a generator. The installer
must make sure that the total square inches of free air inlet
opening is sufficient to limit the heat rise in the room to
prevent the room temperature from exceeding the generator 's
operating temperature.
Figure 8. Louver
Find the actual free air opening as follows:
Figure 9. Screening and Expanded Metal
Screening and Expanded Metal: Screening and expanded metal may
be used to cover air inlet and outlet openings in a structure that
houses the generator. These materials also offer a restriction to
the free flow of cooling air, which must be compensated for by
making the actual air opening in the structure proportionally
larger. Screening and expanded metal are usually assigned a "free
air inlet area" value by the manufacturer, which is given as a
percentage.
To find the actual size of the air inlet opening needed, proceed
as follows:
Example 1: If the required inlet air opening area on a
particular generator is 400 square inches and the building air
opening is to be covered with screening having a 70% "free air
inlet area":
Divide 400 square inches by 0.70, to obtain 576 square inches.
Actual air inlet opening size in the building should be equal to
or greater than 576 square inches. (An opening that measures 24 X
24 inches (576 square inches) would be adequate in this case to
achieve the required 1125 Cu. ft/minute (31.86 Cubic Meters/Min.).
Example 2: The required inlet air opening area on a particular generator is 500 square inches and the building air opening is to be covered with screening having a 70% "free air inlet area":
Divide 500 square inches by 0.70, to obtain 714 square inches.
Actual air inlet opening size in the building should be greater
than 714 square inches. (An opening that measures 27 X 27 inches
(729 square inches) would be adequate in this case to achieve the
required 2000 Cu. ft/Minute (39 Cubic Meters/Min.).
Tips on Hooking up a Generator (genset) to a Uninterruptible Power System (UPS)
Amazon.com now has tools, tooling and power generators in their Amazon.com's Tool & Home Improvement Store. Click on Amazon's Tool & Home Improvement Store or the logo above to go there or use the Search feature.
If you have questions or comments relating to this flowcharting information, please click here to email the author.
Copyright © Dexter A. Hansen