SECTION 7 - Exhaust System

7-1. General (Exhaust System)

Generator engines give off deadly carbon monoxide gas through their exhaust systems.

Carbon monoxide gas, if breathed in sufficient concentrations, can cause unconsciousness or death. Exhaust gases must be piped safely away from any room or enclosure that houses a generator and to a well ventilated area where people will not be endangered.

Besides the possibility of carbon monoxide poisoning, exhaust piping becomes extremely hot during operation and remains hot for a long time after shutdown. For that reason, the following precautions are necessary:

7-2. General Rules for Exhaust Systems

When installing an exhaust system for a generator, the following rules should be considered:

7-3. Routing Exhaust Piping Through Combustible Walls

Figure 10.  Wall Thimble

Wall Thimble

7-4. Routing Exhaust Piping Through Combustible Roofs

Exhaust piping that passes through any combustible roof must be separated from the roof by a ventilated metal thimble that is at least 6 inches in diameter larger than the piping. The thimble must extend at least 9 inches (229mm)(10 inches (250mm) recommended) above and below roof construction.

Figure 11.  Roof Thimble

Roof Thimble

7-5. Rain Cap

A rain cap is recommended on the end of the exhaust pipe. The rain cap is attached to the end of the pipe and opens due to the pressure from the exhaust discharge force. The rain cap protects the exhaust system from the environment when the system is not running.

7-6. Spark Arrestor

Use of a spark arrestor is required by the U.S. Department of Forestry if located on lands under their jurisdiction. The spark arrestor is recommended in areas where combustible materials may ignite such as dry grass, leaves, or other combustible materials.

7-7. Exhaust Back Pressure

The exhaust back pressure of the generator when measured at full load must not exceed the manufacturer's recommendations. The size of exhaust pipe, number and type of ends and fittings together with the selection and location of muffler determine exhaust back pressure.

A typical 90 degree bend in an exhaust system is equal to adding 8 feet (2.67 meters) of pipe.

SECTION 8 - Gaseous Fuel Systems

8-1. General (Gaseous Fuel Systems)

Some generators are equipped with fuel systems that utilize Liquefied Petroleum (LP) or Natural Gas as a fuel.

Local fuel gas codes may vary widely. For that reason, it is recommended that a local gas distributor or installer be consulted when installing a gaseous fuel supply system. In the absence of local fuel gas codes and regulation, booklets published by the National Fire Protection Association (NFPA) may be used as sources of information.

The installer must ensure that the correct fuel delivery system is installed, and that applicable standards and codes are strictly complied with.

8-2.  Advantages of Gaseous Fuels

Use of Natural and LP gas as a fuel may result in a slight power loss. However, that disadvantage is usually compensated for by the many advantages of gaseous fuels. Some of the advantages of gaseous fuels are:

Low residue content, resulting in minimum carbon formation.

8-3. Gaseous Fuel System Variations

Any one of four different types of gaseous fuel systems may typically be installed by the factory on your generator system, dependent upon the model. These are:

8-4. Properties of Gaseous Fuels

Natural Gas: Is lighter than air and tends to settle in high places. Natural gas is found in the gaseous state only at normal ambient conditions. Natural gas is highly explosive and accumulations of the gas can be ignited at the slightest spark. For that reason, adequate ventilation is absolutely essential and fuel lines must be free of leaks. Local fuel/gas codes usually dictate the maximum pressure at which natural gas can enter a structure. A primary regulator is required, to reduce the pressure of the delivered gas to the reduced pressure required by code.

LP Gas: Is heavier than air, tends to settle in low places. The gas is highly explosive and the slightest spark can cause an explosion. LP gas is usually supplied in pressure tanks as a liquid, but is found in gaseous form at normal atmospheric temperature and pressure. It may consist of (1) butane, or (2) propane, or (3) a mixture of these two gases. Fuel suppliers may fill the supply tank with a mixture made up primarily of butane in warm weather. Butane may not provide sufficient vapor pressure in colder weather and more propane may have to be added to the mixture. The ratio of butane to propane is especially important when a large outdoor supply tank is used. LP gas must be converted to its vapor state before it enters the engine carburetor.

8-5. Natural Gas Fuel System

The maximum pressure at which natural gas can enter the building is established by code and may vary from area to area. The gas distribution company will usually provide piping from the main distribution line to the standby generator site. A primary regulator is needed to reduce gas supply pressures to the required safe level before the gas enters a building. Such a regulator may or may not be provided by the gas supplier. It is the responsibility of the gas supplier to ensure that sufficient gas pressure is available to operate the primary regulator.

Gas outlet pressure from the primary regulator to the standby generator's shutoff valve should typically not exceed approximately 0.50 pounds per square inch (psi), or 14 inches of water column. Optimum supply pressure to most small generator's shutoff valve is 11 inches of water column. Depending on the characteristics of the specific shutoff valve in use, the valve may or may not open at supply pressures greater than 0.50 psi (14 inches water column).

Install a flexible length of fuel line between rigid piping and the Generator engine's natural gas connection point.

Natural gas is delivered to the primary regulator. From the primary regulator, in most installations, the gas flows through a solenoid operated fuel shutoff valve, a pressure reducing valve and the engine's natural gas carburetor. The shutoff valve is electrically energized open during startup and running, is de-energized closed on shutdown. The carburetor measures engine air flow and meters gas to the engine based on throttle setting and load. The carburetor also provides a positive gas shutoff.

8-6. LP Gas Vapor Withdrawal System

This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10-20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state.

Ambient temperatures around the supply tank must be high enough to sustain adequate vaporization or the system will not function properly. In addition to the cooling effects of ambient air, the vaporization process itself provides an additional cooling effect. Vapor withdrawal systems are generally more suited for smaller engines that need less fuel.

When ambient temperatures are low and fuel consumption is high, the vapor withdrawal system may not function efficiently. This is particularly true with larger engine machines.

Many LP gas and Natural Gas vaporous fuel systems are identical as a demand regulator is used to provide fuel to the engine.

8-7. LP Liquid Withdrawal System

This type of system delivers gas in liquid form to a generator. The liquid fuel must then be vaporized before it is delivered to the engine carburetor.

Liquid withdrawal (LP) gas systems usually employ a "vaporizer-regulator" to convert the liquid to its vapor state. A "vaporizer-regulator" is mounted in the air flow of the engine to provide heat to the regulator for fuel vaporization.

LP liquid withdrawal is typically used for equipment used in remote locations where size and availability of refilling the tank is limited. Liquid withdrawal is also used for trailered and construction site equipment.

8-8. Dual Natural/LP Gas Fuel System

In some areas, the cost of Natural gas may be reduced considerably by procuring the gas on "interrupted service" rates. Such "interrupted service" can be obtained by using LP gas as an emergency fuel whenever Natural gas is not available.. Automatic changeover is accomplished by using two regulators - a line pressure regulator for natural gas and a vacuum operated regulator for LP gas. The differences in pressures compensates for the greater BTU value of LP gas.

During operation on Natural gas, a 5 inch (water column) (typical) pressure exists in the common line to the carburetor. This pressure closes the LP gas regulator. Loss of Natural gas pressure causes loss of pressure in the line; the LP gas regulator then opens to admit LP gas into the system. A separate power mixture adjustment in the LP gas line provides precise setting of air/fuel ratios for each of the two fuels. Changeover is automatic with the engine operating.

8-9. Gaseous Fuel System Piping

The following general rules apply to piping used in gaseous fuel systems:

NOTE: In the absence of local purging and leak test standards, NFPA No. 54 may be used as a guide.


8-10. Gaseous Fuel Pipe Sizes

A "Gas Flow Pipe Sizing Chart" (Table 8-1) is provided below. Use the chart to determine the correct piping diameter in gaseous fuel systems (such as Natural gas and LP gas vapor withdrawal type).

To find the proper pipe diameter, the installer must know (a) the length of the gas piping run, and (b) the cubic feet of gas needed by the generator when under full load.

First, find the length of the piping run on the chart.

From the pipe length figure on the chart, move horizontally across the chart until you reach a number that is just higher than the cubic feet of gas needed under full load. From the cubic feet of gas figure, move straight up vertically in the chart to the pipe diameter given in that vertical column. This is the pipe size required.

LP Gaseous Fuel Example: A small 16 horse power generator when operating at full load requires a supply of 51 cubic feet per hour of LP gas. Length of the piping run from the supply tank is 60 feet. Propane gas having a specific gravity of 1.5 and with a multiplier of 0.633 is used (Table 8-2). From the pipe length in the chart, trace horizontally across to "86" (the first number larger than 51 cubic feet). Moving vertically upward in the chart, a 3/4 inch pipe is needed. Applying the chart conversion factor (86 x 0.633=54.44) and the 3/4 inch pipe is still adequate.

Natural Gas Example: A small 16 horse power generator operating at full load requires 115 cubic feet per hour of Natural gas. Length of the piping run from the supply tank is 75 feet. Natural gas having a specific gravity of 0.65 and with a multiplier of 0.962 (Table 8-2) is to be used. From the pipe length in the chart, trace horizontally across to "155" (the first number larger than 115 cubic feet). Moving vertically upward in the chart, a 1 inch pipe is required. Apply the conversion factor (155 x 0.962=149.1) and the 1 inch pipe is still adequate.

Table 8-1.  Gas Flow Pipe Sizing Chart

Length of
pipe (FT/M)

1/2 In.
(12.7mm)

3/4 In.
(19.05mm)

1 In.
(25.4mm)

1-1/4 In.
(31.75mm)

1-1/2 In.
(38.1mm)

2 In.
(50.8mm)

2-1/2 In.
(68.5mm)

3 In.
(76.2mm)

4 In.
(101.6mm)

6 In.
(152.4mm)

8 In.
(203.2)

15/4.57

76

172

345

750

1220

2480

3850

6500

13880

28700

79000

30/9.14

52

120

241

535

850

1780

2750

4700

9700

27370

55850

45/13.72

43

99

199

435

700

1475

2300

3900

7900

23350

45600

60/18.29

38

86

173

380

610

1290

2000

3450

6800

19330

39500

75/22.86

70

155

345

545

1120

1750

3000

6000

17310

35300

90/27.43

77

141

310

490

1000

1560

2700

5500

15800

32250

105/32.00

65

131

280

450

920

1430

2450

5100

14620

29850

120/36.58

120

270

420

860

1340

2300

4800

13680

27980

150/45.72

109

242

380

780

1220

2090

4350

12240

25000

180/54.86

100

225

350

720

1120

1950

4000

11160

22800

210/64.01

92

205

320

660

1030

1780

3700

10330

21100

240/73.15

190

300

620

970

1680

3490

9600

19740

270/82.30

178

285

580

910

1580

3250

9000

18610

300/91.44

170

270

545

860

1490

3000

8500

17660

450/137.16

140

226

450

710

1230

2500

7000

14420

600/182.88

119

192

390

900

1030

2130

6000

12480

Table 8-2.  Chart Conversion Factors

Specific
Gravity

Multiplier

Specific
Gravity

Multiplier

Specific
Gravity

Multiplier

0.50

1.100

0.700

0.926

1.200

0.707

0.55

1.040

0.800

0.867

1.400

0.655

0.60

1.000

0.900

0.817

1.500

0.633

0.65

0.962

1.000

0.775

1.700

0.594

Note 1:  Use of elbows increases pressure drop on fuel lines.  A 90 degree elbow adds 3 to 8 feet of equivalent length to your pipe estimate.

Note 2:  Typical Specific Gravity for Natural Gas is 0.65.

Note 3:  Typical Specific Gravity for LP is 1.5.


Back to Table of Contents

Go to APPENDIX A - Applicable Codes

Tips on Hooking up a Generator (genset) to a Uninterruptible Power System (UPS)


Amazon.com

Dexter Hansen
Publications

Uninterruptible Power Products Logo

SmartDraw logo
English   German

JobGenie
12,700 job Descriptions
on CD ROM



The author of these publications can be reached by clicking here or call 952/906-3501.

Amazon.com now has tools, tooling and gas powered generators in their Amazon.com's Home Improvement Store.  Click on Amazon.com's Home Improvement Store or the logo below to go there or use the Search feature.

Amazon.com



 
LEGAL PAGE


Copyright © Dexter A. Hansen